Measurement functions Measurement range Display range Resolution Accuracy
Fault loop impedance
Fault loop ZL-PE, ZL-N, ZL-L 0.13 Ω…1999 Ω acc. to IEC 61557 0.00 Ω…1999 Ω from 0.01 Ω ±(5% m.v. + 3 digits)
Fault loop ZL-PE in RCD mode from 0.50 Ω…1999 Ω acc. to IEC 61557 0.00 Ω…1999 Ω from 0.01 Ω from ±(6% m.v. + 5 digits)
Measurements of RCD parameters
RCD tripping test and measurement of tripping time tA measuring current 0,5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
general and short-time delay RCD 0 ms…300 ms 0 ms…300 ms 1 ms ±(2% m.v. + 2 digits)
selective RCD 0 ms…500 ms 0 ms…500 ms 1 ms ±(2% m.v. + 2 digits)
Measurement of RCD tripping current IA measuring current 0.2 IΔn…2.0 IΔn
for sinusoidal residual current (AC type) 3.0 mA…1000 mA 3.0 mA…1000 mA from 0.1 mA ±5% IΔn
for unidirectional residual current and unidirectional with the 6 mA DC bias (type A) 3.5 mA…700 mA 3.5 mA…700 mA from 0.1 mA ±10% IΔn
for direct residual current (type B) 2.0 mA…1000 mA 2.0 mA…1000 mA from 0.1 mA ±10% IΔn
Earth resistance
3-pole method from 0.5 Ω…1.99 kΩ acc. to IEC 61557-5 0.00 Ω…1.99 kΩ from 0.01 Ω from ±(2% m.v. + 3 digits)
Insulation resistance
Measuring voltage 50 V 50 kΩ…250 MΩ acc. to IEC 61557-2 0 kΩ…250 MΩ from 1 kΩ from ±(3% m.v. + 8 digits)
Measuring voltage 100 V 100 kΩ…500 MΩ acc. to IEC 61557-2 0 kΩ…500 MΩ from 1 kΩ from ±(3% m.v. + 8 digits)
Measuring voltage 250 V 250 kΩ…999 MΩ acc. to IEC 61557-2 0 kΩ…999 MΩ from 1 kΩ from ±(3% m.v. + 8 digits)
Measuring voltage 500 V 500 kΩ…2.00 GΩ acc. to IEC 61557-2 0 kΩ…2,00 GΩ from 1 kΩ from ±(3% m.v. + 8 digits)
Measuring voltage 1000 V 1000 kΩ…3.00 GΩ acc. to IEC 61557-2 0 kΩ…3,00 GΩ from 1 kΩ from ±(3% m.v. + 8 digits)
Resistance of protective conductors and equipotential bondings
Measurement of resistance of protective conductors and equipotential bondings with ±200 mA curren 0.12 Ω…400 Ω acc. to IEC 61557-4 0.00 Ω…400 Ω from 0.01 Ω ±(2% m.v. + 3 digits)
Measurement of resistance with low current 0,0 Ω…1999 Ω 0,0 Ω…1999 Ω from 0.1 Ω ±(3% m.v. + 3 digits)
Phase sequence indication in the same direction (correct). opposite direction (incorrect). UL-L voltage: 95 V…500 V (45 Hz…65 Hz)
Power measurement 0.0 VA…200 000 VA, 0.0 W…200 000 W, 0.0 var…200 000 var 0.0 VA…200 000 VA, 0.0 W…200 000 W, 0.0 var…200 000 var from 0.1 VA, from 0.1 W, from 0.1 var from ±(7% m.v. + 3 digits)

“m.v.” – measured value

Description

Professional measurements for every budget

Versatile yet simple to use, the Sonel MPI-520 multifunctional meter for electrical installations performs its tasks flawlessly when measuring the parameters of electrical installations. The instrument has been developed to meet the needs of installers as well as measurement engineers. Intuitive operation will allow beginners to use the device, while advanced measuring capabilities will meet the expectations of the most demanding specialists. A number of modern solutions have been applied in the meter, which translate into additional functions and greater capabilities of the device.