Search

PQM-700

SPESIFIKASI

Parameters

Parameter Measuring range Max. resolution Accuracy
Alternating voltage (TRMS) 0.0…760.0 V 4 significant digits ±0.5% Unom
Crest Factor Voltage 1.00…10.00 (≤1.65 for 690 V voltage 0.01 ±5%
Crest Factor Current 1.00…10.00 (≤3.6 dla Inom) 0.01 ±5%
Alternating current (TRMS) depending on clamp* 4 significant digits ±0.2% Inom (error does not account for clamp error)
Frequency 40.00…70.00 Hz 0.01 Hz ±0.05 Hz
Active, reactive, apparent and distortion power depending on configuration (transducers, clamps) 4 significant digits depending on configuration (transducers, clamps)
Active, reactive and apparent energy depending on configuration (transducers, clamps) 4 significant digits as power error
cosφ and power factor (PF) 0.00…1.00 0.01 ±0.03
tgφ 0,00…10,00 0.01 depends on error of active and reactive power
Harmonics Voltage DC, 1…40 as for alternating voltage True RMS ±0,15% Unom for m.v. < 3% Unom
±5% m.v. for m.v. ≥ 3% Unom
Harmonics Current DC, 1…40 as for alternating current True RMS ±0.5% Inom for m.v. < 10% Inom
±5% m.v. for m.v. ≥ 10% Inom
THD Voltage and current 0.0..100.0% (relative to RMS value) 0.1% ±5%
Flicker index 0.40…10.00 0.01 ±10%
Unbalance factor Voltage and current 0.0…10.0% 0.1% ±0.3% (absolute error)

m.v. – measured value

*

  • F-1A1, F-2A1, F-3A1 clamp: 0…1500 A AC (5000 Ap-p)
  • F-1A, F-2A, F-3A clamp: 0…3000 A AC (10 000 Ap-p)
  • F-1A6, F-2A6, F-3A6 clamp: 0…6000 A AC (20 000 Ap-p)
  • C-4A clamp: 0…1000 A AC (3600 Ap-p)
  • C-5A clamp: 0…1000 A AC/DC (3600 Ap-p)
  • C-6A clamp: 0..10 A AC (36 Ap-p)
  • C-7A clamp: 0…100 A AC (360 Ap-p)

Description

Resistant to any conditions, the Sonel PQM-700 power quality analyser is an effective device for analysing and recording network parameters. Based on advanced technology, the Sonel PQM-700 power quality analyser is effective for measuring, analysing and recording 50/60 Hz power network parameters. It is also used to control the quality of electricity in accordance with the European standard EN 50160 and the Regulation of the Minister of Economy of 4 May 2007 on detailed conditions for the operation of the power system. The extensive measurement capabilities of this device will be appreciated by a wide range of users who need a portable device to check the quality of electricity. The Sonel PQM-700 meets the demanding standards of the IEC 61000 standard for Class S analysers related to measurement uncertainties and measurement methods. This meter model is intended for those users who do not need a Class A analyser, as the PQM-700 provides comprehensive measurements of power quality parameters in Class S in accordance with IEC 61000-4-30.