SPESIFIKASI

Measurement functions Measurement range Display range Resolution Accuracy
Interference voltage 0 V…100 V 0 V…100 V 1 V ±(2% m.v. + 3 digits)
Connection and equipotential bonding resistance 0.13 Ω…199 Ω acc. to EN 61557-4 0.00 Ω…199 Ω from 0.01 Ω ±(2% m.v. + 3 digits)
Earth resistance
2-wire method 0.00 Ω…1.99 kΩ 0.00 Ω…1.99 kΩ from 0.01 Ω from ±(2% m.v. + 3 digits)
3-wire method 0.50 Ω…1.99 kΩ acc. to EN 61557-5 0.00 Ω…1.99 kΩ from 0.01 Ω ±(2% m.v. + 3 digits)
auxiliary electrodes resistance 0 Ω…50.0 kΩ 0 Ω…50.0 kΩ from 1 Ω ±(5% (RE +RH+RS) + 3 digits)

“m.v.” – measured value

Category

Description

Basic measurements of earthing systems and continuity of connections

The Sonel MRU-21 earth resistance meter is a simple meter which makes it possible to measure earthing with the use of the technical method and to measure the continuity of protective and equalising connections.